Why is Maximo not sending e-mail? Mail server properties, the communication log and failed messages

Maximo hands every e-mail to one mail (SMTP) server named in System Properties. If that server is not set, templates, escalation notifications and workflow e-mails are created but never delivered.

Versions: On Maximo Application Suite 9.1 we confirmed, read-only, that the same mail properties, default values, template settings, the SEND_FAILED action and all the messages below are present (17 November 2026), after reading the same on Maximo 7.6.1.2 (4 November 2026). Both checks were read-only: neither system has a mail server, so we have not sent or failed an e-mail on either version.

IBM’s page: IBM’s current Maximo Manage documentation says: “a communication log lists the inbound and outbound communications for a record, such as a ticket or work order.”

Last checked: 17 November 2026

How it works

The mail properties on the lab system (names and descriptions as Maximo stores them):

PropertyWhat it does
mail.smtp.hostThe name of the SMTP mail server. Empty = no mail.
mail.smtp.portMail server port.
mail.smtp.ssl.enable, mail.smtp.starttls.enableEncryption to the mail server.
mxe.smtp.user, mxe.smtp.passwordMail server login, if the server needs one.
mxe.smtp.connectiontimeout, mxe.smtp.timeoutTime-outs in milliseconds (default 180000).
mxe.adminEmailThe Maximo administrator’s address, also the fallback sender.
mail.smtp.sendpartialSend to the valid addresses when some are invalid.
mxe.email.content.type, mxe.email.convertToPlainTextHTML or plain text.
mail.debugJavaMail debug output.

The communication log. When a template has Comm Log Entry ticked (it is ticked on every delivered template), each send writes a log row against the record, with recipients, subject, message and date. It shows on the record’s Communication Log tab.

Failed messages. With Track Failed Messages ticked on the template, a failed send is kept in the communication log and marked as failed. Maximo does not retry by itself. IBM’s documented way is an escalation that runs the delivered action SEND_FAILED on records with failed log rows. That action is delivered on both systems we read; only the escalation has to be built. No delivered template had tracking on.

Remember: a communication log row proves that Maximo created the e-mail, not that it was delivered.

Steps

  1. System Properties: set mail.smtp.host, and the port, encryption, user and password if your server needs them. Set mxe.adminEmail.
  2. Live-refresh the properties. (Whether these mail properties take effect without a restart was not tested.)
  3. Give each sending user a primary e-mail address in People, or rely on mxe.adminEmail. Message BMXAA9507E describes the order: the user’s address, then mxe.adminEmail, else no communication.
  4. On each template, keep Comm Log Entry. Tick Track Failed Messages where you need retries.
  5. For retries, build an escalation on the record’s object whose condition finds records with failed log rows, and give its point the action SEND_FAILED. Run the condition as a query first: a backlog can mail many people at once.
  6. To diagnose, in Logging set mail to DEBUG and create a COMMTEMPLATE logger at INFO if it is missing. Attach an appender, Apply Settings, and read the server log. On Maximo Application Suite the server log is a container log; IBM’s APIs for administrative utilities page describes how to download log files.

Where it breaks

How we checked it

On a Maximo 7.6.1.2 lab system we read the mail properties and their values, the communication log, the logger table, the SEND_FAILED action and the message texts, all with read-only queries. We then read the same on a Maximo Application Suite 9.1 system. Neither system has a mail server, so nothing was sent and nothing was changed.

Not tested: setting a mail server, a failed send, and the SEND_FAILED retry.